INSTALLATION INSTRUCTIONS
ELECTRONIC OIL IGNITER
24 VDC
Electrical Shock Hazard
Electrical shock can cause severe personal
injury or death.
Disconnect all electrical power to the burner before servicing.
More than one disconnect switch may be in the supply circuit.
Installation and service must only be performed by a quali ed
service technician.
Remove all jewelry, such as rings and watches before servicing.
Provide ground wiring to the burner, metal control enclosures
and accessories. (This may also be required to aid proper control
system operation).
y
y
y
y
APPLICATION INFORMATION:
This igniter is designed for use with 24 VDC.
It is rated for continuous duty and can be used with
intermittent, or interrupted ignition primary controls.
The Beckett oil igniter is designed to mount in the same
manner as standard ignition transformers and igniters.
This igniter can be adapted to multiple base plates to
accommodate Beckett ADC & SDC burners. It will also t
on many other vendors’ transformer base plates.
CAUTION! Do not use this igniter beyond its design
speci cations. Improper operation and igniter failure may
result.
SPECIFICATIONS:
Input Voltage: 21.6 - 32 Vdc
Output Voltage: 19 kV peak
Output Current: 35 mA RMS
Input Current: 1.2A
Ambient Operating Temperature: -40 to +150° F
Storage Temperature: -40 to +150° F
Moisture: 5 to 95% Relative Humidity, Condensing
Table 1 - Complete Igniter Base Plate Assemblies
Part No. Burner Models
5218501U Beckett ADC 24 VDC
5218502U Beckett SDC 24 VDC
Installation Instructions:
(If base plate is already installed, skip to step number 9)
Locate the igniter input leads.
Install the 32743 igniter gasket and route the leads through
the appropriate base plate lead exit hole. Make sure these
leads are not being crushed.
Mount the igniter ush to base plate with the mounting screws
supplied.
Note: Use #6 x 7/16” screws when using the bottom mounting
holes. Use #10 thread forming paint scraping screws, if using
the two top mounting holes for 5218501 & 5218502.
Tighten all screws securely.
Install the barrier and base plate gaskets for Beckett Model
ADC only.
Use gaskets for other burner models, as required by the
manufacturer.
Use of top mounting screws is possible for Beckett Models
ADC and SDC.
Mount the assembled unit to the burner using the screws
supplied.
Use “paint scraping” screws for all burners (2 at the hinge and
2 for non-hinged base plates). Tighten these screws securely
to provide effective grounding to burner housing.
Verify the burner is properly grounded.
Install the cad cell if applicable.
Carefully route the igniter input and cad cell leads to prevent
them from being pinched during closing.
Wiring Igniter to GeniSys 24 VDC Primary Control
Carefully follow the control, or equipment manufacturer’s
wiring instructions and diagrams.
Fasten cad cell leads to control CAD CELL spade
terminals.
Attach the Black lead with insulated ag terminal to the
primary control GND (IGN) spade terminal.
Connect the Blue-White striped lead with insulated ag
terminal to the primary control IGNITER spade terminal.
Verify the igniter secondary output terminals are correctly
arranged to make good electrical contact with the oil burner
electrodes.
Close the igniter. Install and securely tighten the two front
base plate retaining screws (4 screws, if no hinge).
Reconnect electric power to the burner circuit.
Verify with instruments that the burner is adjusted to the
manufacturer’s recommended settings
Cycle the burner several times to verify prompt and smooth
ignition. Verify proper operating and limit control operation
before leaving.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
Vue de la page 0
1 2

Résumé du contenu

Page 1 - ELECTRONIC OIL IGNITER

INSTALLATION INSTRUCTIONSELECTRONIC OIL IGNITER ● 24 VDCElectrical Shock HazardElectrical shock can cause severe personal injury or death.Disconnect a

Page 2 - BECKETT CORPORATION

R.W. BECKETT CORPORATIONP.O. Box 1289, Elyria, Ohio 44036R.W. BECKETT CANADA, LTD430 Laird, Unit 3, Guelph, Ontario, N1G 3X7Part No. 61829 R00, Print

Commentaires sur ces manuels

Pas de commentaire